Headline
Siemens TeleControl Server Basic
As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens’ ProductCERT Security Advisories (CERT Services | Services | Siemens Global). View CSAF
- EXECUTIVE SUMMARY CVSS v4 9.3 ATTENTION: Exploitable remotely/low attack complexity Vendor: Siemens Equipment: TeleControl Server Basic Vulnerability: Missing Authentication for Critical Function
- RISK EVALUATION Successful exploitation of this vulnerability could allow an unauthenticated remote attacker to obtain password hashes of users and to login to and perform authenticated operations of the database service.
- TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS Siemens reports that the following products are affected: TeleControl Server Basic V3.1: Version V3.1.2.2 and up to but not including V3.1.2.3 3.2 VULNERABILITY OVERVIEW 3.2.1 MISSING AUTHENTICATION FOR CRITICAL FUNCTION CWE-306 The affected application contains an information disclosure vulnerability. This could allow an unauthenticated remote attacker to obtain password hashes of users and to login to and perform authenticated operations of the database service. CVE-2025-40765 has been assigned to this vulnerability. A CVSS v3.1 base score of 9.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H). A CVSS v4 score has also been calculated for CVE-2025-40765. A base score of 9.3 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N). 3.3 BACKGROUND CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing COUNTRIES/AREAS DEPLOYED: Worldwide COMPANY HEADQUARTERS LOCATION: Germany 3.4 RESEARCHER Tenable reported this vulnerability to Siemens. Siemens reported this vulnerability to CISA.
- MITIGATIONS Siemens has identified the following specific workarounds and mitigations users can apply to reduce risk: TeleControl Server Basic V3.1: Restrict access to port 8000 on the affected systems to trusted IP addresses only TeleControl Server Basic V3.1: Update to V3.1.2.3 or later version As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens’ operational guidelines for industrial security and following recommendations in the product manuals. Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage. For more information see the associated Siemens security advisory SSA-062309 in HTML and CSAF. CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as: Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet. Locate control system networks and remote devices behind firewalls and isolating them from business networks. When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs). Recognize VPNs may have vulnerabilities, should be updated to the most recent version available, and are only as secure as the connected devices. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures. CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies. CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets. Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies. Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents. No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time.
- UPDATE HISTORY October 16, 2025: Initial Republication of Siemens ProductCERT SSA-062309