Source
us-cert
View CSAF 1. EXECUTIVE SUMMARY CVSS v4 9.3 ATTENTION: Exploitable remotely/low attack complexity Vendor: Rockwell Automation Equipment: FactoryTalk ThinManager Vulnerabilities: Missing Authentication For Critical Function, Out-of-Bounds Read 2. RISK EVALUATION Successful exploitation of these vulnerabilities could allow an attacker to send crafted messages to the device resulting in database manipulation or a denial-of-service condition. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following Rockwell Automation FactoryTalk product versions are affected: ThinManager: Versions 11.2.0 to 11.2.9 ThinManager: Versions 12.0.0 to 12.0.7 ThinManager: Versions 12.1.0 to 12.1.8 ThinManager: Versions 13.0.0 to 13.0.5 ThinManager: Versions 13.1.0 to 13.1.3 ThinManager: Versions 13.2.0 to 13.2.2 ThinManager: Version 14.0.0 3.2 Vulnerability Overview 3.2.1 MISSING AUTHENTICATION FOR CRITICAL FUNCTION CWE-306 An authentication vulnerability exists in the affected product. The vulnerability could al...
As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens' ProductCERT Security Advisories (CERT Services | Services | Siemens Global). View CSAF 1. EXECUTIVE SUMMARY CVSS v4 10.0 ATTENTION: Exploitable remotely/low attack complexity Vendor: Siemens Equipment: InterMesh Vulnerabilities: OS Command Injection, Missing Authentication for Critical Function, Execution with Unnecessary Privileges, Incorrect Privilege Assignment 2. RISK EVALUATION Successful exploitation of these vulnerabilities could allow an attacker to perform remote code execution, execute commands, write arbitrary files, or execute arbitrary commands. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following versions of Siemens InterMesh Subscriber Devices, a wireless alarm reporting system, are affected: InterMesh 7177 Hybrid 2.0 Subscriber: All...
View CSAF 1. EXECUTIVE SUMMARY CVSS v4 9.3 ATTENTION: Exploitable remotely/low attack complexity Vendor: Delta Electronics Equipment: InfraSuite Device Master Vulnerability: Deserialization of Untrusted Data 2. RISK EVALUATION Successful exploitation of this vulnerability could allow an unauthenticated attacker to remotely execute arbitrary code. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following versions of InfraSuite Device Master, a real-time device monitoring software, are affected: InfraSuite Device Master: Versions 1.0.12 and prior 3.2 Vulnerability Overview 3.2.1 DESERIALIZATION OF UNTRUSTED DATA CWE-502 Delta Electronics InfraSuite Device Master versions prior to 1.0.12 are affected by a deserialization vulnerability that targets the Device-Gateway, which could allow deserialization of arbitrary .NET objects prior to authentication, resulting in remote code execution. CVE-2024-10456 has been assigned to this vulnerability. A CVSS v3.1 base score of 9.8 has been calculated...
View CSAF 1. EXECUTIVE SUMMARY CVSS v4 5.1 ATTENTION: Exploitable remotely/low attack complexity/public exploits are available Vendor: Solar-Log Equipment: Base 15 Vulnerability: Improper Neutralization of Input During Web Page Generation ('Cross-site Scripting') 2. RISK EVALUATION Successful exploitation of this vulnerability could result in an attacker obtaining unauthorized access. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following versions of Solar-Log Base 15 are affected: Base 15: Firmware 6.0.1 Build 161 3.2 Vulnerability Overview The affected product is vulnerable to a cross-site scripting attack, which may allow an attacker to bypass access controls and gain unauthorized access. CVE-2023-46344 has been assigned to this vulnerability. A CVSS v3.1 base score of 5.4 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:L/UI:R/S:C/C:L/I:L/A:N). A CVSS v4 score has also been calculated for CVE-2023-46344. A base score of 5.1 has been calculated; the CVSS vecto...
View CSAF 1. EXECUTIVE SUMMARY CVSS v4 7.1 ATTENTION: low attack complexity/public exploits are available Vendor: Deep Sea Electronics Equipment: DSE855 Vulnerability: Missing Authentication for Critical Function 2. RISK EVALUATION Successful exploitation of this vulnerability could allow an attacker to access stored credentials. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following versions of Deep Sea Electronics DSE855, an ethernet communications device, are affected: DSE855: Version 1.0.26 3.2 Vulnerability Overview 3.2.1 Missing Authentication for Critical Function CWE-306 Deep Sea Electronics DSE855 is vulnerable to a configuration disclosure when direct object reference is made to the Backup.bin file using an HTTP GET request. CVE-2024-5947 has been assigned to this vulnerability. A CVSS v3.1 base score of 6.5 has been calculated; the CVSS vector string is (AV:A/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N). A CVSS v4 score has also been calculated for CVE-2024-5947. A base score of 7.1 ha...
View CSAF 1. EXECUTIVE SUMMARY CVSS v4 8.6 ATTENTION: Exploitable remotely/low attack complexity Vendor: iniNet Solutions Equipment: SpiderControl SCADA PC HMI Editor Vulnerability: Path Traversal 2. RISK EVALUATION Successful exploitation of this vulnerability could allow an attacker to gain remote control of the device. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following versions of iniNet Solutions SpiderControl SCADA PC HMI Editor, a software management platform, are affected: SpiderControl SCADA PC HMI Editor: Version 8.10.00.00 3.2 Vulnerability Overview 3.2.1 Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal') CWE-22 iniNet Solutions SpiderControl SCADA PC HMI Editor has a path traversal vulnerability. When the software loads a malicious ‘ems' project template file constructed by an attacker, it can write files to arbitrary directories. This can lead to overwriting system files, causing system paralysis, or writing to startup items, resulting in r...
View CSAF 1. EXECUTIVE SUMMARY CVSS v4 6.9 ATTENTION: Exploitable remotely/low attack complexity/public exploits are available Vendor: VIMESA Equipment: VHF/FM Transmitter Blue Plus Vulnerability: Improper Access Control 2. RISK EVALUATION Successful exploitation of this vulnerability could allow an attacker to perform a Denial-of-Service. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following version of VIMESA VHF/FM Transmitter Blue Plus, a VHF/FM Transmitter, is affected: VHF/FM Transmitter Blue Plus: Version v9.7.1 3.2 Vulnerability Overview 3.2.1 Improper Access Control CWE-284 VIMESA VHF/FM Transmitter Blue Plus is suffering from a Denial-of-Service (DoS) vulnerability. An unauthenticated attacker can issue an unauthorized HTTP GET request to the unprotected endpoint 'doreboot' and restart the transmitter operations. CVE-2024-9692 has been assigned to this vulnerability. A CVSS v3.1 base score of 5.3 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:...
View CSAF 1. EXECUTIVE SUMMARY CVSS v3 7.8 ATTENTION: Low attack complexity Vendor: ICONICS, Mitsubishi Electric Equipment: ICONICS Product Suite, Mitsubishi Electric MC Works64 Vulnerability: Incorrect Default Permissions 2. RISK EVALUATION Successful exploitation of this vulnerability could result in disclosure of confidential information, data tampering, or a denial-of-service condition. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS ICONICS reports that the following versions of ICONICS and Mitsubishi Electric Products are affected: ICONICS Suite including GENESIS64, Hyper Historian, AnalytiX, and MobileHMI: Version 10.97.3 and prior Mitsubishi Electric MC Works64: all versions 3.2 Vulnerability Overview 3.2.1 Incorrect Default Permissions CWE-276 There is an incorrect default permissions vulnerability in ICONICS and Mitsubishi Electric products which may allow a disclosure of confidential information, data tampering, or a denial of service condition due to incorrect default permission...
View CSAF 1. EXECUTIVE SUMMARY CVSS v4 7.1 ATTENTION: Exploitable remotely/low attack complexity Vendor: HMS Networks Equipment: EWON FLEXY 202 Vulnerability: Insufficiently Protected Credentials 2. RISK EVALUATION Successful exploitation of this vulnerability could allow an attacker to sniff and decode credentials that are transmitted using weak encoding techniques. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following versions of EWON FLEXY 202, an industrial modular gateway, are affected: EWON FLEXY 202: Firmware Version 14.2s0 3.2 Vulnerability Overview 3.2.1 CWE-522: Insufficiently Protected Credentials The EWON FLEXY 202 transmits credentials using a weak encoding method base64. An attacker who is present in the network can sniff the traffic and decode the credentials. CVE-2024-7755 has been assigned to this vulnerability. A CVSS v3.1 base score of 8.2 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:R/S:C/C:H/I:L/A:N). CVE-2024-7755 has been assigned to this ...
View CSAF 1. EXECUTIVE SUMMARY CVSS v4 7.0 ATTENTION: Exploitable remotely/low attack complexity Vendor: LCDS - Leão Consultoria e Desenvolvimento de Sistemas Ltda ME Equipment: LAquis SCADA Vulnerability: Cross-site Scripting 2. RISK EVALUATION Successful exploitation of this vulnerability could allow an attacker to steal cookies, inject arbitrary code, or perform unauthorized actions. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following versions of LAquis SCADA, an HMI program, are affected: LAquis SCADA: Version 4.7.1.511 3.2 Vulnerability Overview 3.2.1 IMPROPER NEUTRALIZATION OF INPUT DURING WEB PAGE GENERATION ('CROSS-SITE SCRIPTING') CWE-79 In LAquis SCADA version 4.7.1.511, a cross-site scripting vulnerability could allow an attacker to inject arbitrary code into a web page. This could allow an attacker to steal cookies, redirect users, or perform unauthorized actions. CVE-2024-9414 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.1 has been calculated; ...