Source
us-cert
View CSAF 1. EXECUTIVE SUMMARY CVSS v4 9.3 ATTENTION: Exploitable remotely/low attack complexity Vendor: mySCADA Equipment: myPRO Vulnerabilities: Improper Neutralization of Special Elements used in an OS Command ('OS Command Injection') 2. RISK EVALUATION Successful exploitation of these vulnerabilities could allow a remote attacker to execute arbitrary commands or disclose sensitive information. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following mySCADA products are affected: myPRO Manager: Versions prior to 1.3 myPRO Runtime: Versions prior to 9.2.1 3.2 VULNERABILITY OVERVIEW 3.2.1 Improper Neutralization of Special Elements used in an OS Command ('OS Command Injection') CWE-78 mySCADA myPRO does not properly neutralize POST requests sent to a specific port with email information. This vulnerability could be exploited by an attacker to execute arbitrary commands on the affected system. CVE-2025-20061 has been assigned to this vulnerability. A CVSS v3.1 base score of 9.8 has be...
View CSAF 1. EXECUTIVE SUMMARY CVSS v3 7.8 ATTENTION: Low attack complexity Vendor: Schneider Electric Equipment: Easergy Studio Vulnerability: Improper Privilege Management 2. RISK EVALUATION Successful exploitation of this vulnerability may risk unauthorized access to the installation directory for Easergy Studio, which could allow an attacker with access to the file system to elevate privileges. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS Schneider Electric reports that the following Easergy Studio products are affected: Easergy Studio: Versions 9.3.1 and prior 3.2 VULNERABILITY OVERVIEW 3.2.1 IMPROPER PRIVILEGE MANAGEMENT CWE-269 An improper privilege management vulnerability exists that could cause unauthorized access, loss of confidentiality, integrity, and availability of the workstation when a non-administrative authenticated user tries to perform privilege escalation by tampering with the binaries. CVE-2024-9002 has been assigned to this vulnerability. A CVSS v3 base score of 7...
View CSAF 1. EXECUTIVE SUMMARY CVSS v3 8.5 ATTENTION: Low attack complexity Vendor: Schneider Electric Equipment: EVlink Home Smart and Schneider Charge Vulnerability: Cleartext Storage of Sensitive Information 2. RISK EVALUATION Successful exploitation of this vulnerability may expose test credentials in the firmware binary. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS Schneider Electric reports that the following EVlink Home Smart and Schneider Charge charging stations are affected: EVlink Home Smart: All versions prior to 2.0.6.0.0 Schneider Charge: All versions prior to 1.13.4 3.2 VULNERABILITY OVERVIEW 3.2.1 CLEARTEXT STORAGE OF SENSITIVE INFORMATION CWE-312 A cleartext storage of sensitive information vulnerability exists that exposes test credentials in the firmware binary. CVE-2024-8070 has been assigned to this vulnerability. A CVSS v3 base score of 8.5 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:N/S:C/C:H/I:L/A:L). 3.3 BACKGROUND CRITICAL INFRASTR...
View CSAF 1. EXECUTIVE SUMMARY CVSS v4 4.6 ATTENTION: Low attack complexity Vendor: Schneider Electric Equipment: EcoStruxure Power Build Rapsody Vulnerability: Improper Restriction of Operations within the Bounds of a Memory Buffer 2. RISK EVALUATION Successful exploitation of this vulnerability could allow local attackers to potentially execute arbitrary code when opening a malicious project file. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS Schneider Electric reports the following versions of EcoStruxure Power Build, a configuration program for panel builders, are affected: EcoStruxure Power Build Rapsody: Version v2.5.2 NL and prior EcoStruxure Power Build Rapsody: Version v2.7.1 FR and prior EcoStruxure Power Build Rapsody: Version v2.7.5 ES and prior EcoStruxure Power Build Rapsody: Version v2.5.4 INT and prior 3.2 VULNERABILITY OVERVIEW 3.2.1 IMPROPER RESTRICTION OF OPERATIONS WITHIN THE BOUNDS OF A MEMORY BUFFER CWE-119 An improper restriction of operations within the bounds of a...
View CSAF 1. EXECUTIVE SUMMARY CVSS v4 6.9 ATTENTION: Low attack complexity Vendor: HMS Networks Equipment: Ewon Flexy 202 Vulnerability: Cleartext Transmission of Sensitive Information 2. RISK EVALUATION Successful exploitation of this vulnerability could allow an attacker to disclose sensitive user credentials. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following HMS Networks products are affected: Ewon Flexy 202: All versions 3.2 VULNERABILITY OVERVIEW 3.2.1 Cleartext Transmission of Sensitive Information CWE-319 EWON Flexy 202 transmits user credentials in clear text with no encryption when a user is added, or user credentials are changed via its webpage. CVE-2025-0432 has been assigned to this vulnerability. A CVSS v3.1 base score of 5.7 has been calculated; the CVSS vector string is (AV:A/AC:L/PR:N/UI:R/S:U/C:H/I:N/A:N). A CVSS v4 score has also been calculated for CVE-2025-0432. A base score of 6.9 has been calculated; the CVSS vector string is (AV:A/AC:L/AT:N/PR:N/UI:P/VC:H...
View CSAF 1. EXECUTIVE SUMMARY CVSS v4 5.9 ATTENTION: Exploitable from an adjacent network/low attack complexity Vendor: ZF Equipment: RSSPlus Vulnerability: Authentication Bypass By Primary Weakness 2. RISK EVALUATION Successful exploitation of this vulnerability could allow an unauthenticated attacker to remotely (proximal/adjacent with RF equipment) call diagnostic functions which could impact both the availability and integrity. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following versions of RSSPlus are affected: RSSPlus 2M: build dates 01/08 through at least 01/23 3.2 VULNERABILITY OVERVIEW 3.2.1 AUTHENTICATION BYPASS BY PRIMARY WEAKNESS CWE-305 The affected product is vulnerable to an authentication bypass vulnerability targeting deterministic RSSPlus SecurityAccess service seeds, which may allow an attacker to remotely (proximal/adjacent with RF equipment or via pivot from J2497 telematics devices) call diagnostic functions intended for workshop or repair scenarios. This ca...
As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens' ProductCERT Security Advisories (CERT Services | Services | Siemens Global). View CSAF 1. EXECUTIVE SUMMARY CVSS v4 7.2 ATTENTION: Exploitable remotely/low attack complexity Vendor: Siemens Equipment: SIMATIC S7-1200 CPUs Vulnerability: Cross-Site Request Forgery 2. RISK EVALUATION Successful exploitation of this vulnerability could allow an unauthenticated attacker to change the CPU mode by tricking a legitimate and authenticated user with sufficient permissions on the target CPU to click on a malicious link. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS Siemens reports that the following products are affected: SIMATIC S7-1200 CPU 1211C AC/DC/Rly (6ES7211-1BE40-0XB0): Versions prior to V4.7 SIMATIC S7-1200 CPU 1214C DC/DC/DC (6ES7214-1AG40-0XB0): Version...
View CSAF 1. EXECUTIVE SUMMARY CVSS v4 7.1 ATTENTION: Exploitable from adjacent network Standard: Traffic Alert and Collision Avoidance System (TCAS) II Equipment: Collision Avoidance Systems Vulnerabilities: Reliance on Untrusted Inputs in a Security Decision, External Control of System or Configuration Setting 2. RISK EVALUATION Successful exploitation of these vulnerabilities could allow an attacker to manipulate safety systems and cause a denial-of-service condition. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following revisions of TCAS II are affected: TCAS II: Versions 7.1 and prior 3.2 Vulnerability Overview 3.2.1 Reliance on Untrusted Inputs in a Security Decision CWE-807 By utilizing software-defined radios and a custom low-latency processing pipeline, RF signals with spoofed location data can be transmitted to aircraft targets. This can lead to the appearance of fake aircraft on displays and potentially trigger undesired Resolution Advisories (RAs). CWE-2024-9310 has been...
As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens' ProductCERT Security Advisories (CERT Services | Services | Siemens Global). View CSAF 1. EXECUTIVE SUMMARY CVSS v4 7.1 ATTENTION: Exploitable remotely/low attack complexity Vendor: Siemens Equipment: SIPROTEC 5 Vulnerability: Files or Directories Accessible to External Parties 2. RISK EVALUATION Successful exploitation of this vulnerability could allow an authenticated remote attacker to read arbitrary files or the entire filesystem of the device. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS Siemens reports that the following products are affected: Siemens SIPROTEC 5 6MD84 (CP300): Versions prior to 9.80 Siemens SIPROTEC 5 7SA87 (CP300): Versions 7.80 up to but not including 9.80 Siemens SIPROTEC 5 7SD82 (CP100): Versions 7.80 and after Siemens SIPROTEC...
View CSAF 1. EXECUTIVE SUMMARY CVSS v4 8.5 ATTENTION: Low attack complexity Vendor: Fuji Electric Equipment: Alpha5 SMART Vulnerability: Stack-based Buffer Overflow 2. RISK EVALUATION Successful exploitation of this vulnerability could allow an attacker to execute arbitrary code. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following versions of Fuji Electric Alpha5 SMART, a servo drive system, are affected: Alpha5 SMART: Versions 4.5 and prior 3.2 VULNERABILITY OVERVIEW 3.2.1 STACK-BASED BUFFER OVERFLOW CWE-121 The affected product is vulnerable to a stack-based buffer overflow, which may allow an attacker to execute arbitrary code. CVE-2024-34579 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.8 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H). A CVSS v4 score has also been calculated for CVE-2024-34579. A base score of 8.5 has been calculated; the CVSS vector string is (CVSS4.0/AV:L/AC:L/AT:N/PR:N/UI:P/VC:H/VI:H/VA:H/SC:N/SI...