mySCADA myPRO Manager

View CSAF 1. EXECUTIVE SUMMARY CVSS v4 10.0 ATTENTION: Exploitable remotely/low attack complexity Vendor: mySCADA Equipment: myPRO Vulnerabilities: OS Command Injection, Improper Authentication, Missing Authentication for Critical Function, Path Traversal. 2. RISK EVALUATION Successful exploitation of this vulnerability could allow a remote attacker to execute arbitrary commands or disclose sensitive information. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following mySCADA products are affected: myPRO Manager: Versions prior to 1.3 myPRO Runtime: Versions prior to 9.2.1 3.2 Vulnerability Overview 3.2.1 Improper Neutralization of Special Elements used in an OS Command ('OS Command Injection') CWE-78 A parameter within a command does not properly validate input within myPRO Manager which could be exploited by an unauthenticated remote attacker to inject arbitrary operating system commands. CVE-2024-47407 has been assigned to this vulnerability. A CVSS v3.1 base score of 10.0 has been...

us-cert
#vulnerability#web#perl#auth
Schneider Electric Modicon M340, MC80, and Momentum Unity M1E

View CSAF 1. EXECUTIVE SUMMARY CVSS v4 7.7 ATTENTION: Exploitable remotely Vendor: Schneider Electric Equipment: Modicon M340, MC80, and Momentum Unity M1E Vulnerabilities: Improper Enforcement of Message Integrity During Transmission in a Communication Channel, Authentication Bypass by Spoofing 2. RISK EVALUATION Successful exploitation of these vulnerabilities could allow an attacker to retrieve password hashes or cause a denial-of-service condition. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following versions of Schneider Electric Modicon M340, MC80, and Momentum Unity M1E are affected: Modicon M340 CPU (part numbers BMXP34*): All versions (CVE-2024-8933) Modicon M340 CPU (part numbers BMXP34*): versions after SV3.60 (CVE-2024-8935) Modicon MC80 (part numbers BMKC80): All versions (CVE-2024-8933) Modicon Momentum Unity M1E Processor (171CBU*): All versions (CVE-2024-8933) 3.2 Vulnerability Overview 3.2.1 Improper Enforcement of Message Integrity During Transmission in a Communi...

OSCAT Basic Library

View CSAF 1. EXECUTIVE SUMMARY CVSS v4 5.1 ATTENTION: Low attack complexity Vendor: CODESYS GmbH Equipment: OSCAT Basic Library Vulnerability: Out-of-bounds Read 2. RISK EVALUATION Successful exploitation of this vulnerability allows an local, unprivileged attacker to access limited internal data of the PLC, which may lead to a crash of the affected service. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following versions CODESYS OSCAT, are affected: CODESYS OSCAT Basic Library: Version 3.3.5.0 oscat.de OSCAT Basic Library: Versions 3.3.5 and prior oscat.de OSCAT Basic Library: Versions 335 and prior 3.2 Vulnerability Overview 3.2.1 OUT-OF-BOUNDS READ CWE-125 The affected product is vulnerable to an out-of-bounds read in the OSCAT Basic Library, which allows a local, unprivileged attacker to access limited internal data of the PLC which may lead to a crash of the affected service. CVE-2024-6876 has been assigned to this vulnerability. A CVSS v3.1 base score of 5.1 has been calculated;...

Automated Logic WebCTRL Premium Server

View CSAF 1. EXECUTIVE SUMMARY CVSS v4 10.0 ATTENTION: Exploitable remotely/low attack complexity Vendor: Automated Logic Equipment: WebCTRL Premium Server Vulnerabilities: Unrestricted Upload of File with Dangerous Type, URL Redirection to Untrusted Site ('Open Redirect') 2. RISK EVALUATION Successful exploitation of these vulnerabilities could allow an unauthenticated remote attacker to execute arbitrary commands on the server hosting WebCTRL or redirect legitimate users to malicious sites. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following Automated Logic products are affected: Automated Logic WebCTRL® Server : Version 7.0 Carrier i-Vu: Version 7.0 Automated Logic SiteScan Web: Version 7.0 Automated Logic WebCTRL for OEMs: Version 7.0 3.2 Vulnerability Overview 3.2.1 UNRESTRICTED UPLOAD OF FILE WITH DANGEROUS TYPE CWE-434 A vulnerability in Automated Logic WebCTRL 7.0 allows an unauthenticated user to upload files of dangerous types without restrictions, which could lead to re...

Schneider Electric EcoStruxure IT Gateway

View CSAF 1. EXECUTIVE SUMMARY CVSS v4 10.0 ATTENTION: Exploitable remotely/low attack complexity Vendor: Schneider Electric Equipment: EcoStruxure IT Gateway Vulnerability: Missing Authorization 2. RISK EVALUATION Successful exploitation of this vulnerability could allow unauthorized access. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS Schneider Electric reports that the following versions of EcoStruxure IT Gateway are affected: EcoStruxure IT Gateway: 1.21.0.6 EcoStruxure IT Gateway: 1.22.0.3 EcoStruxure IT Gateway: 1.22.1.5 EcoStruxure IT Gateway: 1.23.0.4 3.2 Vulnerability Overview 3.2.1 MISSING AUTHORIZATION CWE-862 A missing authorization vulnerability exists that could cause unauthorized access when enabled on the network and potentially impacting connected devices. CVE-2024-10575 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H). A CVSS v4 score has also been calculate...

Schneider Electric Modicon M340, MC80, and Momentum Unity M1E

View CSAF 1. EXECUTIVE SUMMARY CVSS v4 9.2 ATTENTION: Exploitable remotely Vendor: Schneider Electric Equipment: Modicon M340, MC80, and Momentum Unity M1E Vulnerabilities: Improper Input Validation, Improper Restriction of Operations within the Bounds of a Memory Buffer 2. RISK EVALUATION Successful exploitation of these vulnerabilities could allow an attacker to tamper with memory on these devices. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following versions of Schneider Electric Modicon M340, MC80, and Momentum Unity M1E are affected: Modicon M340 CPU (part numbers BMXP34*): Versions prior to SV3.65 Modicon MC80 (part numbers BMKC80)(CVE-2024-8937, CVE-2024-8938): All versions Modicon Momentum Unity M1E Processor (171CBU*)(CVE-2024-8937, CVE-2024-8938): All versions 3.2 Vulnerability Overview 3.2.1 Improper Input Validation CWE-20 An Input Validation vulnerability exists that could lead to loss of confidentiality of controller memory after a successful Man-In-The-Middle attack ...

Mitsubishi Electric MELSEC iQ-F Series

View CSAF 1. EXECUTIVE SUMMARY CVSS v3 7.5 ATTENTION: Exploitable remotely/low attack complexity Vendor: Mitsubishi Electric Corporation Equipment: MELSEC iQ-F Series Vulnerability: Improper Validation of Specified Type of Input 2. RISK EVALUATION Successful exploitation of this vulnerability could allow a remote attacker to cause a denial-of-service condition in Ethernet communication on the module. A system reset of the module is required for recovery. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS Mitsubishi Electric reports that the following versions of MELSEC iQ-F Series Ethernet module and EtherNet/IP module are affected: MELSEC iQ-F Series FX5-ENET: version 1.100 and later MELSEC iQ-F Series FX5-ENET/IP: version 1.100 to 1.104 3.2 Vulnerability Overview 3.2.1 Improper Validation of Specified Type of Input CWE-1287 A denial-of-service vulnerability due to improper validation of a specified type of input exists in MELSEC iQ-F Ethernet Module and EtherNet/IP Module. CVE-2024-8403 has ...

Rockwell Automation FactoryTalk Updater

View CSAF 1. EXECUTIVE SUMMARY CVSS v4 9.1 ATTENTION: Exploitable remotely/low attack complexity Vendor: Rockwell Automation Equipment: FactoryTalk Updater Vulnerabilities: Insecure Storage of Sensitive Information, Improper Input Validation, Improperly Implemented Security Check for Standard 2. RISK EVALUATION Successful exploitation of these vulnerabilities could result in an authentication bypass, remote code execution, and/or a local privilege escalation 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following versions of FactoryTalk are affected: FactoryTalk Updater - Web Client: Version 4.00.00 FactoryTalk Updater - Client: All versions FactoryTalk Updater - Agent: All versions 3.2 Vulnerability Overview 3.2.1 INSECURE STORAGE OF SENSITIVE INFORMATION CWE-922 An authentication bypass vulnerability exists due to shared secrets across accounts, which could allow a threat actor to impersonate a user if the threat actor is able to enumerate additional information required during auth...

Rockwell Automation Verve Asset Manager

View CSAF 1. EXECUTIVE SUMMARY CVSS v4 8.6 ATTENTION: Exploitable remotely/low attack complexity Vendor: Rockwell Automation Equipment: Verve Asset Manager Vulnerability: Dependency on Vulnerable Third-Party Component 2. RISK EVALUATION Successful exploitation of this vulnerability could lead to arbitrary code execution. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following versions of Verve Asset Manager are affected: Verve Asset Manager: Versions 1.39 and prior 3.2 Vulnerability Overview 3.2.1 DEPENDENCY ON VULNERABLE THIRD-PARTY COMPONENT CWE-1395 Verve Asset Manager utilizes Kibana, which contains a remote code execution vulnerability that allows an attacker with access to ML and alerting connecting features as well as write access to internal ML to trigger a prototype pollution vulnerability, which can ultimately lead to arbitrary code execution. The code execution is limited to the container. CVE-2024-37287 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.2...

Siemens Mendix Runtime

As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens' ProductCERT Security Advisories (CERT Services | Services | Siemens Global). View CSAF 1. EXECUTIVE SUMMARY CVSS v4 6.9 ATTENTION: Exploitable remotely/low attack complexity Vendor: Siemens Equipment: Mendix Runtime Vulnerability: Concurrent Execution using Shared Resource with Improper Synchronization ('Race Condition') 2. RISK EVALUATION Successful exploitation of this vulnerability could allow unauthenticated remote attackers to circumvent default account lockout measures. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following versions of Mendix Runtime are affected: Mendix Runtime: V8 Mendix Runtime: V9 Mendix Runtime: V10 Mendix Runtime: V10.6 Mendix Runtime: V10.12 3.2 Vulnerability Overview 3.2.1 CONCURRENT EXECUTION USING SHARED RESOURCE WITH...