Source
us-cert
As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens' ProductCERT Security Advisories (CERT Services | Services | Siemens Global). View CSAF 1. EXECUTIVE SUMMARY CVSS v4 8.7 ATTENTION: Exploitable remotely/low attack complexity Vendor: Siemens Equipment: SIPROTEC 5 Devices Vulnerability: Use of Default Credentials 2. RISK EVALUATION Successful exploitation of this vulnerability could allow an unauthenticated, remote attacker to retrieve sensitive information of the device. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS Siemens reports that the following products are affected: Siemens SIPROTEC 5 7VE85 (CP300): Version V8.80 up to but not including V9.90 Siemens SIPROTEC 5 7SS85 (CP300): Version V8.80 up to but not including V9.90 Siemens SIPROTEC 5 Communication Module ETH-BB-2FO (Rev. 2): All versions prior t...
As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens' ProductCERT Security Advisories (CERT Services | Services | Siemens Global). View CSAF 1. EXECUTIVE SUMMARY CVSS v4 9.4 ATTENTION: Exploitable remotely/low attack complexity Vendor: Siemens Equipment: Opcenter Intelligence Vulnerabilities: Improper Authentication, Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal'), Deserialization of Untrusted Data, Insertion of Sensitive Information into Log File, Server-Side Request Forgery (SSRF) 2. RISK EVALUATION Successful exploitation of these vulnerabilities could enable an attacker to execute remote code or allow a malicious site administrator to change passwords for users. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS Siemens reports that the following products are affected: Siemens O...
As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens' ProductCERT Security Advisories (CERT Services | Services | Siemens Global). View CSAF 1. EXECUTIVE SUMMARY CVSS v4 8.7 ATTENTION: Exploitable remotely/low attack complexity Vendor: Siemens Equipment: SIMATIC PCS neo and TIA Administrator Vulnerability: Insufficient Session Expiration 2. RISK EVALUATION Successful exploitation of this vulnerability could allow a remote unauthenticated attacker, who has obtained the session token by other means, to re-use a legitimate user's session even after logout. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS Siemens reports that the following products are affected: SIMOCODE ES V19: Versions prior to V19 Update 1 TIA Administrator: Versions 3.0.4 and prior SIMATIC PCS neo V4.1: Versions prior to V4.1 Update 2 SIMATIC P...
View CSAF 1. EXECUTIVE SUMMARY CVSS v4 8.6 ATTENTION: Exploitable remotely/low attack complexity/known public exploitation Vendor: Trimble Equipment: Cityworks Vulnerability: Deserialization of Untrusted Data 2. RISK EVALUATION Successful exploitation of this vulnerability could allow an authenticated user to perform a remote code execution. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following versions of Trimble Cityworks, an asset and work management system, are affected: Cityworks: All versions prior to 23.10 3.2 VULNERABILITY OVERVIEW 3.2.1 DESERIALIZATION OF UNTRUSTED DATA CWE-502 Trimble Cityworks versions prior to 23.10 are vulnerable to a deserialization vulnerability. This could allow an authenticated user to perform a remote code execution attack against a customer's Microsoft Internet Information Services (IIS) web server. CVE-2025-0994 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.2 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:H/UI...
View CSAF 1. EXECUTIVE SUMMARY CVSS v3 7.1 ATTENTION: Exploitable remotely Vendor: Schneider Electric Equipment: EcoStruxure Power Monitoring Expert (PME) Vulnerability: Deserialization of Untrusted Data 2. RISK EVALUATION Successful exploitation of this vulnerability could allow an attacker to remotely execute code. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS Schneider Electric reports that the following products are affected: EcoStruxure Power Monitoring Expert (PME): Versions 2022 and prior 3.2 VULNERABILITY OVERVIEW 3.2.1 DESERIALIZATION OF UNTRUSTED DATA CWE-502 A deserialization of untrusted data vulnerability exists which could allow code to be remotely executed on the server when unsafely deserialized data is posted to the web server. CVE-2024-9005 has been assigned to this vulnerability. A CVSS v3 base score of 7.1 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:L/UI:R/S:U/C:H/I:H/A:H). 3.3 BACKGROUND CRITICAL INFRASTRUCTURE SECTORS: Commercial Facilities, C...
View CSAF 1. EXECUTIVE SUMMARY CVSS v4 8.5 ATTENTION: Low attack complexity Vendor: Schneider Electric Equipment: EcoStruxure Vulnerability: Uncontrolled Search Path Element 2. RISK EVALUATION Successful exploitation of this vulnerability allows for local privilege escalation, which could lead to the execution of a malicious Dynamic-Link Library (DLL). 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following Schneider Electric EcoStruxure products and versions, which incorporate Revenera FlexNet Publisher, are affected: EcoStruxure Control Expert: Versions prior to V16.1 EcoStruxure Process Expert: All versions EcoStruxure OPC UA Server Expert: All versions EcoStruxure Control Expert Asset Link: Versions prior to V4.0 SP1 EcoStruxure Machine SCADA Expert Asset Link: All versions EcoStruxure Architecture Builder: Versions prior to V7.0.18 EcoStruxure Operator Terminal Expert: All versions Vijeo Designer: Version prior to V6.3SP1 HF1 EcoStruxure Machine Expert including EcoStruxure Machi...
View CSAF 1. EXECUTIVE SUMMARY CVSS v4 9.3 ATTENTION: Exploitable remotely/low attack complexity Vendor: ABB Equipment: Drive Composer Vulnerability: Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal') 2. RISK EVALUATION Successful exploitation of this vulnerability could allow attackers unauthorized access to the file system on the host machine. An attacker can exploit this flaw to run malicious code, which could lead to the compromise of the affected system. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS ABB reports that the following Drive Composer products are affected: Drive Composer entry: Version 2.9.0.1 and prior Drive Composer pro: Version 2.9.0.1 and prior 3.2 VULNERABILITY OVERVIEW 3.2.1 IMPROPER LIMITATION OF A PATHNAME TO A RESTRICTED DIRECTORY ('PATH TRAVERSAL') CWE-22 A vulnerability in drive composer can allow attackers unauthorized access to the file system on the host machine. An attacker can exploit this flaw to run malicious code, which could ...
View CSAF 1. EXECUTIVE SUMMARY CVSS v4 6.1 ATTENTION: Exploitable remotely Vendor: Schneider Electric Equipment: Pro-face GP-Pro EX and Remote HMI Vulnerability: Improper Enforcement of Message Integrity During Transmission in a Communication Channel 2. RISK EVALUATION Successful exploitation of this vulnerability could allow man-in-the-middle attacks, resulting in information disclosure, integrity issues, and operational failures. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following versions of Pro-face GP-Pro EX and Remote HMI are affected: Pro-face GP-Pro EX: All versions Pro-face Remote HMI: All versions 3.2 VULNERABILITY OVERVIEW 3.2.1 IMPROPER ENFORCEMENT OF MESSAGE INTEGRITY DURING TRANSMISSION IN A COMMUNICATION CHANNEL CWE-924 The affected products are vulnerable to an improper enforcement of message integrity during transmission in a communication channel vulnerability that could cause partial loss of confidentiality, loss of integrity, and availability of the HMI when at...
View CSAF 1. EXECUTIVE SUMMARY CVSS v4 8.7 ATTENTION: Exploitable remotely/low attack complexity Vendor: Schneider Electric Equipment: Modicon M580 PLCs, BMENOR2200H and EVLink Pro AC Vulnerability: Incorrect Calculation of Buffer Size 2. RISK EVALUATION Successful exploitation of this vulnerability could cause a denial-of-service of the product when an unauthenticated user sends a crafted HTTPS packet to the webserver. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following versions of Modicon M580 PLCs, BMENOR2200H and EVLink Pro AC are affected: Modicon M580 CPU (part numbers BMEP* and BMEH*, excluding M580 CPU Safety): Versions prior to SV4.30 Modicon M580 CPU Safety (part numbers BMEP58-S and BMEH58-S): Versions prior to SV4.21 BMENOR2200H: All versions EVLink Pro AC: Versions prior to v1.3.10 3.2 VULNERABILITY OVERVIEW 3.2.1 INCORRECT CALCULATION OF BUFFER SIZE CWE-131 The affected product is vulnerable to an incorrect calculation of buffer size vulnerability which could cause a...
View CSAF 1. EXECUTIVE SUMMARY CVSS v4 9.3 ATTENTION: Exploitable remotely/low attack complexity Vendor: AutomationDirect Equipment: C-more EA9 HMI Vulnerability: Buffer Copy without Checking Size of Input ('Classic Buffer Overflow') 2. RISK EVALUATION Successful exploitation of this vulnerability could allow an attacker to cause a denial-of-service condition or achieve remote code execution on the affected device. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following Automation Direct products are affected: C-more EA9 HMI EA9-T6CL: v6.79 and prior C-more EA9 HMI EA9-T7CL-R: v6.79 and prior C-more EA9 HMI EA9-T7CL: v6.79 and prior C-more EA9 HMI EA9-T8CL: v6.79 and prior C-more EA9 HMI EA9-T10CL: v6.79 and prior C-more EA9 HMI EA9-T10WCL: v6.79 and prior C-more EA9 HMI EA9-T12CL: v6.79 and prior C-more EA9 HMI EA9-T15CL-R: v6.79 and prior C-more EA9 HMI EA9-T15CL: v6.79 and prior C-more EA9 HMI EA9-RHMI: v6.79 and prior 3.2 VULNERABILITY OVERVIEW 3.2.1 Buffer Copy without Checking S...