As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens' ProductCERT Security Advisories (CERT Services | Services | Siemens Global). View CSAF 1. EXECUTIVE SUMMARY CVSS v4 8.7 ATTENTION: Exploitable remotely/low attack complexity Vendor: Siemens Equipment: User Management Component (UMC) Vulnerabilities: Out-of-bounds Read, Out-of-bounds Write 2. RISK EVALUATION Successful exploitation of these vulnerabilities could allow an unauthenticated remote attacker to cause a denial-of-service condition. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS Siemens reports that the following products are affected: Siemens SIMATIC PCS neo V4.1: All versions Siemens SIMATIC PCS neo V5.0: All versions Siemens SINEC NMS: All versions Siemens SINEMA Remote Connect: All versions Siemens Totally Integrated Automation Portal (TIA Port...
View CSAF 1. EXECUTIVE SUMMARY CVSS v4 8.6 ATTENTION: Exploitable remotely/low attack complexity Vendor: ECOVACS Equipment: DEEBOT Vacuum and Base Station Vulnerabilities: Use of Hard-coded Cryptographic Key, Download of Code Without Integrity Check 2. RISK EVALUATION Successful exploitation of these vulnerabilities could allow an attacker to send malicious updates to the devices or execute code. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS ECOVACS reports the following DEEBOT vacuum and base station devices are affected: X1S PRO: Versions prior to 2.5.38 X1 PRO OMNI: Versions prior to 2.5.38 X1 OMNI: Versions prior to 2.4.45 X1 TURBO: Versions prior to 2.4.45 T10 Series: Versions prior to 1.11.0 T20 Series: Versions prior to 1.25.0 T30 Series: Versions prior to 1.100.0 3.2 VULNERABILITY OVERVIEW 3.2.1 Use of Hard-coded Cryptographic Key CWE-321 ECOVACS robot vacuums and base stations communicate via an insecure Wi-Fi network with a deterministic WPA2-PSK. The key can be easily derived f...
As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens' ProductCERT Security Advisories (CERT Services | Services | Siemens Global). View CSAF 1. EXECUTIVE SUMMARY CVSS v4 2.1 ATTENTION: Exploitable remotely Vendor: Siemens Equipment: Mendix OIDC SSO Vulnerability: Incorrect Privilege Assignment 2. RISK EVALUATION Successful exploitation of this vulnerability could allow an attacker to modify the system and gain administrator read/write privileges. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS Siemens reports the following products are affected: Siemens Mendix OIDC SSO (Mendix 9 compatible): All versions Siemens Mendix OIDC SSO (Mendix 10 compatible): All versions before V4.0.0 3.2 VULNERABILITY OVERVIEW 3.2.1 INCORRECT PRIVILEGE ASSIGNMENT CWE-266 The Mendix OIDC SSO module grants read and write access to all...
View CSAF 1. EXECUTIVE SUMMARY CVSS v4 8.5 ATTENTION: Low attack complexity Vendor: ABB Equipment: Automation Builder Vulnerabilities: Incorrect Permission Assignment for Critical Resource 2. RISK EVALUATION Successful exploitation of these vulnerabilities could allow an attacker to overrule the Automation Builder's user management. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following versions of Automation Builder are affected: Automation Builder: All versions 3.2 VULNERABILITY OVERVIEW 3.2.1 INCORRECT PERMISSION ASSIGNMENT FOR CRITICAL RESOURCE CWE-732 The affected products store all user management information in the project file. Despite the password data being fully encrypted, an attacker could try to modify parts of the Automation Builder project file by specially crafting contents so the user management will be overruled. CVE-2025-3394 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:L/UI:N/S:U/...
View CSAF 1. EXECUTIVE SUMMARY CVSS v4 9.4 ATTENTION: Exploitable remotely/low attack complexity Vendor: Hitachi Energy Equipment: MACH GWS products Vulnerabilities: Improper Neutralization of Special Elements in Data Query Logic, Improper Limitation of a Pathname to a Restricted Directory, Authentication Bypass by Capture-replay, Missing Authentication for Critical Function 2. RISK EVALUATION Successful exploitation of these vulnerabilities could allow an attacker to inject code, read or modify files, hijack user sessions, or access exposed ports without authentication. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following versions of Hitachi Energy products are affected: MACH GWS: Version 2.1.0.0 (CVE-2024-4872, CVE-2024-3980) MACH GWS: Versions 2.2.0.0 to 2.4.0.0 (CVE-2024-4872, CVE-2024-3980) MACH GWS: Versions 3.0.0.0 to 3.3.0.0 (CVE-2024-4872, CVE-2024-3980, CVE-2024-3982) MACH GWS: Versions 3.1.0.0 to 3.3.0.0 (CVE-2024-7940) 3.2 VULNERABILITY OVERVIEW 3.2.1 IMPROPER NEUTRALIZ...
View CSAF 1. EXECUTIVE SUMMARY CVSS v4 9.3 ATTENTION: Exploitable remotely/low attack complexity Vendor: Hitachi Energy Equipment: Service Suite Vulnerabilities: Use of Less Trusted Source, Inconsistent Interpretation of HTTP Requests ('HTTP Request/Response Smuggling'), Integer Overflow or Wraparound, Out-of-bounds Write, Allocation of Resources Without Limits or Throttling, Exposure of Sensitive Information to an Unauthorized Actor, Memory Allocation with Excessive Size Value, Out-of-bounds Read, Uncontrolled Resource Consumption, Improper Resource Shutdown or Release, Improper Neutralization of CRLF Sequences in HTTP Headers ('HTTP Request/Response Splitting') 2. RISK EVALUATION Successful exploitation of these vulnerabilities could allow an attacker to compromise the confidentiality, integrity, or availability of affected devices. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS Hitachi Energy reports the following products are affected: Service Suite: Versions 9.8.1.3 and prior 3.2 VULN...
View CSAF 1. EXECUTIVE SUMMARY CVSS v4 7.1 ATTENTION: Low attack complexity Vendor: Hitachi Energy Equipment: Relion 670/650/SAM600-IO Series Vulnerability: Buffer Copy without Checking Size of Input ('Classic Buffer Overflow') 2. RISK EVALUATION Successful exploitation of this vulnerability can allow an attacker to reboot the device and cause a denial-of-service condition. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS Hitachi Energy reports the following products are affected: Relion 670/650/SAM600-IO series: Versions 2.2.2.0 up to but not including 2.2.2.6 Relion 670/650/SAM600-IO series: Versions 2.2.3.0 up to but not including 2.2.3.7 Relion 670/650/SAM600-IO series: Versions 2.2.4.0 up to but not including 2.2.4.4 Relion 670/650/SAM600-IO series: Versions 2.2.5.6 up to but not including 2.2.5.6 Relion 670/650/SAM600-IO series: 2.2.0.x Relion 670/650/SAM600-IO series: 2.2.1.x 3.2 VULNERABILITY OVERVIEW 3.2.1 BUFFER COPY WITHOUT CHECKING SIZE OF INPUT ('CLASSIC BUFFER OVERFLOW') CWE-12...
View CSAF 1. EXECUTIVE SUMMARY CVSS v4 8.2 ATTENTION: Exploitable remotely/low attack complexity Vendor: Hitachi Energy Equipment: RTU500 series Vulnerabilities: Improper Neutralization of Input During Web Page Generation ('Cross-site Scripting'), Improper Validation of Specified Index, Position, or Offset in Input 2. RISK EVALUATION Successful exploitation of these vulnerabilities could allow an attacker to execute cross-site scripting or trigger a denial-of-service condition on the affected device. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS Hitachi Energy reports the following products are affected: RTU500 series: Versions 12.0.1 to 12.0.14 RTU500 series: Versions 12.2.1 to 12.2.11 RTU500 series: Versions 12.4.1 to 12.4.11 RTU500 series: Versions 12.6.1 to 12.6.9 RTU500 series: Versions 12.7.1 to 12.7.6 RTU500 series: Versions 13.2.1 to 13.2.6 RTU500 series: Versions 13.4.1 to 13.4.3 3.2 VULNERABILITY OVERVIEW 3.2.1 Improper Neutralization of Input During Web Page Generation ('Cross-...
View CSAF 1. EXECUTIVE SUMMARY CVSS v4 8.2 ATTENTION: Exploitable remotely Vendor: Mitsubishi Electric Equipment: CC-Link IE TSN Remote I/O module, CC-Link IE TSN Analog-Digital Converter module, CC-Link IE TSN Digital-Analog Converter module, CC-Link IE TSN FPGA module, CC-Link IE TSN Remote Station Communication LSI CP620 with GbE-PHY Vulnerability: Improper Validation of Specified Quantity in Input 2. RISK EVALUATION Successful exploitation of this vulnerability could allow an attacker to cause a denial-of-service condition on the affected products. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following versions of Mitsubishi Electric CC-Link IE TSN, a network controller, are affected: CC-Link IE TSN Remote I/O module NZ2GN2S1-32D/32T/32TE/32DT/32DTE: Versions 09 and prior CC-Link IE TSN Remote I/O module NZ2GN2B1-32D/32T/32TE/32DT/32DTE: Versions 09 and prior CC-Link IE TSN Remote I/O module NZ2GNCF1-32D/32T: Versions 09 and prior CC-Link IE TSN Remote I/O module NZ2GNCE3-32D/32D...
View CSAF 1. EXECUTIVE SUMMARY CVSS v4 8.4 ATTENTION: Low attack complexity Vendor: Horner Automation Equipment: Cscape Vulnerability: Out-of-bounds Read 2. RISK EVALUATION Successful exploitation of this vulnerability could allow an attacker to disclose information and execute arbitrary code. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following versions of Horner Automation Cscape, a control system application programming software, are affected: Cscape: Version 10.0 (10.0.415.2) SP1 3.2 VULNERABILITY OVERVIEW 3.2.1 OUT-OF-BOUNDS READ CWE-125 Horner Automation Cscape version 10.0 (10.0.415.2) SP1 is vulnerable to an out-of-bounds read vulnerability that could allow an attacker to disclose information and execute arbitrary code on affected installations of Cscape. CVE-2025-4098 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.8 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H). A CVSS v4 score has also been calculated for CVE-20...