As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens' ProductCERT Security Advisories (CERT Services | Services | Siemens Global). View CSAF 1. EXECUTIVE SUMMARY CVSS v3 7.8 ATTENTION: Exploitable remotely/low attack complexity Vendor: Siemens Equipment: SINEC NMS Vulnerabilities: Incorrect Permission Assignment for Critical Resource, Improper Neutralization of Input During Web Page Generation ('Cross-site Scripting') 2. RISK EVALUATION Successful exploitation of these vulnerabilities could allow an authenticated local attacker to inject arbitrary code and escalate privileges or a remote attacker to perform a stored cross-site scripting(XSS) attack that may lead to unintentional modification of application data by legitimate users. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following products of Sieme...
As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens' ProductCERT Security Advisories (CERT Services | Services | Siemens Global). View CSAF 1. EXECUTIVE SUMMARY CVSS v3 8.0 ATTENTION: Exploitable remotely/low attack complexity Vendor: Siemens Equipment: Simcenter Amesim Vulnerability: Code Injection 2. RISK EVALUATION Successful exploitation of this vulnerability could allow an attacker to perform DLL injection and execute arbitrary code in the context of the affected application process. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following versions of Siemens Simcenter Amesim are affected: Simcenter Amesim: All versions prior to V2021.1 3.2 Vulnerability Overview 3.2.1 Improper Control of Generation of Code ('Code Injection') CWE-94 The affected application contains a SOAP endpoint that could allow ...
View CSAF 1. EXECUTIVE SUMMARY CVSS v3 6.5 ATTENTION: Exploitable remotely/low attack complexity Vendor: Mitsubishi Electric Equipment: CC-Link IE TSN Industrial Managed Switch Vulnerabilities: Observable Timing Discrepancy, Double Free 2. RISK EVALUATION Successful exploitation of these vulnerabilities could result in disclosure of information stored in the product by sending specially crafted packets or could cause a denial-of service (DoS) condition by getting a legitimate user to import a specially crafted certificate 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following versions of Mitsubishi Electric products are affected: CC-Link IE TSN Industrial Managed Switch, model NZ2MHG-TSNT8F2 NZ2MHG-TSNT4: All versions 3.2 Vulnerability Overview 3.2.1 OBSERVABLE TIMING DISCREPANCY CWE-208 An attacker could decrypt ciphertext and disclose sensitive information by sending specially crafted packets and performing a Bleichenbacher style attack. CVE-2022-4304 has been assigned to this vuln...
View CSAF 1. EXECUTIVE SUMMARY CVSS v3 9.8 ATTENTION: Exploitable remotely/low attack complexity Vendor: Hitachi Energy Equipment: AFS65x, AFF66x, AFS67x, AFR67x Series Vulnerabilities: Incorrect Calculation, Integer Overflow or Wraparound, Improper Encoding or Escaping of Output, Exposure of Resource to Wrong Sphere 2. RISK EVALUATION Successful exploitation of these vulnerabilities by an attacker could have a high impact on availability, integrity, and confidentiality of the targeted devices. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following Hitachi Energy products and versions are affected: AFF66X FW: 03.0.02 and prior AFS66X-S: All versions AFS660-C: All versions AFS66X-B: All versions AFS670-V20: All versions AFS65X: All versions AFS67X: All versions AFR677: All versions 3.2 Vulnerability Overview 3.2.1 INCORRECT CALCULATION CWE-682 In Expat (aka libexpat) before 2.4.3, a left shift by 29(or more) places in the storeAtts function in xmlparse.c can lead to realloc misbehavio...
View CSAF 1. EXECUTIVE SUMMARY CVSS v3 10.0 ATTENTION: Exploitable remotely/low attack complexity Vendor: Qognify Equipment: NiceVision Vulnerability: Use of Hard-coded Credentials 2. RISK EVALUATION Successful exploitation of this vulnerability could allow an attacker to retrieve sensitive information about the cameras managed by the platform and its users. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following versions of Qoginfy NiceVision, an IP-video surveillance system, are affected: NiceVision: v3.1 and prior 3.2 Vulnerability Overview 3.2.1 USE OF HARD-CODED CREDENTIALS CWE-798 Qognify NiceVision versions 3.1 and prior are vulnerable to exposing sensitive information using hard-coded credentials. With these credentials an attacker can retrieve information about the cameras, user information, and modify database records. CVE-2023-2306 has been assigned to this vulnerability. A CVSS v3 base score of 10.0 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:C/C:...
View CSAF 1. EXECUTIVE SUMMARY CVSS v3 8.0 ATTENTION: Exploitable remotely/low attack complexity Vendor: DEXMA Equipment: DEXGate Vulnerabilities: Cross-Site Scripting, Cross-Site Request Forgery, Improper Authentication, Cleartext Transmission of Sensitive Information, Exposure of Sensitive Information to an Unauthorized Actor 2. RISK EVALUATION Successful exploitation of these vulnerabilities could result in the attacker impersonating a user, executing arbitrary code, and accessing the connected network. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following version of DEXGate is affected: DEXGate: Version 20130114 3.2 Vulnerability Overview 3.2.1 CROSS-SITE SCRIPTING (XSS) CWE-79 The affected product is vulnerable to a cross-site scripting vulnerability, which could allow an attacker to access the web application to introduce arbitrary Java Script by injecting an XSS payload into the 'hostname' parameter of the vulnerable software. CVE-2023-40153 has been assigned to this vulnerab...
View CSAF 1. EXECUTIVE SUMMARY CVSS v3 9.8 ATTENTION: Exploitable remotely/low attack complexity Vendor: Rockwell Automation Equipment: PanelView 800 Vulnerability: Improper Input Validation 2. RISK EVALUATION Successful exploitation of this vulnerability could allow an attacker to disclose sensitive information, modify data, or cause a denial-of-service. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following versions of Rockwell Automation PanelView 800, a graphics terminal, are affected: PanelView 800 2711R-T10T: V3.011 PanelView 800 2711R-T7T: V3.011 PanelView 800 2711R-T4T: V3.011 3.2 Vulnerability Overview 3.2.1 Improper Input Validation CWE-20 An input/output validation vulnerability exists in a third-party component that the PanelView™ 800 utilizes. Libpng, which is PNG's reference library, version 1.6.32 and earlier does not properly check the length of chunks against the user limit. Libpng versions prior to 1.6.32 are susceptible to a vulnerability which, when successfully e...
View CSAF 1. EXECUTIVE SUMMARY CVSS v3 5.4 ATTENTION: Exploitable remotely/low attack complexity/public exploits are available Vendor: Advantech Equipment: EKI-1524-CE, EKI-1522-CE, EKI-1521-CE Vulnerabilities: Cross-Site Scripting 2. RISK EVALUATION Successful exploitation of these vulnerabilities could allow an attacker to execute code in the context of the session. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following Advantech serial device servers are affected: EKI-1524-CE series: versions 1.24 and prior EKI-1522-CE series: versions 1.24 and prior EKI-1521-CE series: versions 1.24 and prior 3.2 Vulnerability Overview 3.2.1 Cross-Site Scripting CWE-79 Advantech EKI-1524, EKI-1522, EKI-1521 devices through version 1.21 are affected by a stored cross-site scripting vulnerability, which can be triggered by authenticated users in the device name field of the web-interface. CVE-2023-4202 has been assigned to this vulnerability. A CVSS v3 base score of 5.4 has been calculated; the CVS...
View CSAF 1. EXECUTIVE SUMMARY CVSS v3 6.9 ATTENTION: Exploitable remotely/low attack complexity Vendor: Hitachi Energy Equipment: Asset Suite 9 Vulnerability: Improper Authentication 2. RISK EVALUATION Successful exploitation of this vulnerability could allow an authenticated user to enter an arbitrary password to execute equipment tag out actions. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS Hitachi Energy reports these vulnerabilities affect the following products: Asset Suite: Versions 9.6.3.11.1 and prior Asset Suite: Version 9.6.4 3.2 Vulnerability Overview 3.2.1 IMPROPER AUTHENTICATION CWE-287 A vulnerability exists in the Equipment Tag Out authentication, when configured with Single Sign-On (SSO) with password validation in T214. This vulnerability can be exploited by an authenticated user performing an Equipment Tag Out holder action (Accept, Release, and Clear) for another user and entering an arbitrary password in the holder action confirmation dialog box. Despite entering an ...
View CSAF 1. EXECUTIVE SUMMARY CVSS v3 7.5 ATTENTION: Exploitable remotely/low attack complexity Vendor: Baker Hughes - Bently Nevada Equipment: Bently Nevada 3500 System Vulnerabilities: Exposure of Sensitive Information to an Unauthorized Actor, Cleartext Transmission of Sensitive Information, Authentication Bypass by Capture-replay 2. RISK EVALUATION Successful exploitation of these vulnerabilities could allow an attacker to steal sensitive information and gain access to the device. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following versions of the Bently Nevada 3500 System, a real-time monitoring solution, are affected: Bently Nevada 3500 Rack (TDI Firmware): version 5.05 3.2 Vulnerability Overview 3.2.1 EXPOSURE OF SENSITIVE INFORMATION TO AN UNAUTHORIZED ACTOR CWE-200 Baker Hughes – Bently Nevada 3500 System TDI Firmware version 5.05 has a vulnerability in their password retrieval functionality which could be used by an attacker to access passwords stored on the device. CVE...