View CSAF 1. EXECUTIVE SUMMARY CVSS v4 8.6 ATTENTION: Exploitable remotely/low attack complexity Vendor: Rockwell Automation Equipment: FactoryTalk DataMosaix Private Cloud Vulnerabilities: Weak Authentication, Improper Encoding or Escaping of Output 2. RISK EVALUATION Successful exploitation of these vulnerabilities could allow an attacker to take over accounts, steal credentials, redirect users to a malicious website, or bypass MFA. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following versions of FactoryTalk DataMosaix Private Cloud are affected: FactoryTalk DataMosaix Private Cloud: Versions 7.11, 8.00, 8.01 (CVE-2025-11084) FactoryTalk DataMosaix Private Cloud: Versions 7.11, 8.00 (CVE-2025-11085) 3.2 VULNERABILITY OVERVIEW 3.2.1 WEAK AUTHENTICATION CWE-1390 A security issue exists within DataMosaix™ Private Cloud, allowing attackers to bypass MFA during setup and obtain a valid login-token cookie without knowing the users password. This vulnerability occurs when MFA is enabled...
View CSAF 1. EXECUTIVE SUMMARY CVSS v4 9.2 ATTENTION: Exploitable remotely/low attack complexity Vendor: General Industrial Controls Equipment: Lynx+ Gateway Vulnerabilities: Weak Password Requirements, Missing Authentication for Critical Function, Cleartext Transmission of Sensitive Information 2. RISK EVALUATION Successful exploitation of these vulnerabilities could result in obtaining sensitive device information, unauthorized access, or create a denial-of-service condition. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following versions of Lynx+ Gateway are affected: Lynx+ Gateway: Version R08 Lynx+ Gateway: Version V03 Lynx+ Gateway: Version V05 Lynx+ Gateway: Version V18 3.2 VULNERABILITY OVERVIEW 3.2.1 WEAK PASSWORD REQUIREMENTS CWE-521 The affected product is vulnerable to a weak password requirement vulnerability, which may allow an attacker to execute a brute-force attack resulting in unauthorized access and login. CVE-2025-55034 has been assigned to this vulnerability. A C...
As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens' ProductCERT Security Advisories (CERT Services | Services | Siemens Global). View CSAF 1. EXECUTIVE SUMMARY CVSS v4 8.5 ATTENTION: Low attack complexity Vendor: Siemens Equipment: Software Center and Solid Edge Vulnerability: Uncontrolled Search Path Element 2. RISK EVALUATION Successful exploitation of this vulnerability could allow an attacker to execute arbitrary code via placing a crafted DLL file on the system. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following versions of Siemens Software Center and Solid Edge are affected: Siemens Software Center: All versions prior to 3.5 Solid Edge SE2025: All versions prior to V225.0 Update 10 3.2 VULNERABILITY OVERVIEW 3.2.1 UNCONTROLLED SEARCH PATH ELEMENT CWE-427 The affected application is vulnerabl...
View CSAF 1. EXECUTIVE SUMMARY CVSS v4 8.7 ATTENTION: Exploitable remotely/low attack complexity Vendor: Rockwell Automation Equipment: FactoryTalk Policy Manager Vulnerability: Improper Resource Shutdown or Release 2. RISK EVALUATION Successful exploitation of this vulnerability could lead to resource exhaustion and denial of service. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS Rockwell Automation reports that the following versions of FactoryTalk Policy Manager, a software tool that enables OT teams to design, deploy, and manage system-wide security policies using CIP Security and OPC UA standards, are affected: FactoryTalk Policy Manager: Versions 6.51.00 and prior 3.2 VULNERABILITY OVERVIEW 3.2.1 Improper Resource Shutdown or Release CWE-404 A vulnerability in Node.js HTTP servers may allow an attacker to send a specially crafted HTTP request with chunked encoding, which can lead to resource exhaustion and denial of service. The server reads an unbounded number of bytes from a singl...
View CSAF 1. EXECUTIVE SUMMARY CVSS v4 8.6 ATTENTION: Exploitable remotely/low attack complexity Vendor: Rockwell Automation Equipment: AADvance-Trusted SIS Workstation Vulnerability: Path Traversal 2. RISK EVALUATION Successful exploitation of this vulnerability may allow remote code execution. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS Rockwell Automation reports the following versions of AADvance-Trusted SIS Workstation, a software suite for developing and managing safety instrumented system (SIS) applications, are affected: AADvance-Trusted SIS Workstation: Versions 2.00.00 to 2.00.04 3.2 VULNERABILITY OVERVIEW 3.2.1 Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal') CWE-22 A directory traversal vulnerability in DotNetZip v.1.16.0 and earlier may allow a remote attacker to execute arbitrary code via the src/Zip.Shared/ZipEntry.Extract.cs component. Exploitation requires the victim to open a malicious file. CVE-2024-48510 has been assigned to this vulnera...
View CSAF 1. EXECUTIVE SUMMARY CVSS v4 8.4 ATTENTION: Exploitable remotely/low attack complexity Vendor: Rockwell Automation Equipment: Verve Asset Manager Vulnerability: Incorrect Authorization 2. RISK EVALUATION Successful exploitation of this vulnerability could result in an attacker accessing or altering user data. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following versions of Verve Asset Manager, an OT cybersecurity platform, are affected: Verve Asset Manager: Version 1.33 Verve Asset Manager: Version 1.34 Verve Asset Manager: Version 1.35 Verve Asset Manager: Version 1.36 Verve Asset Manager: Version 1.37 Verve Asset Manager: Version 1.38 Verve Asset Manager: Version 1.39 Verve Asset Manager: Version 1.40 Verve Asset Manager: Version 1.41 Verve Asset Manager: Version 1.41.1 Verve Asset Manager: Version 1.41.2 Verve Asset Manager: Version 1.41.3 3.2 VULNERABILITY OVERVIEW 3.2.1 INCORRECT AUTHORIZATION CWE-863 A security issue was discovered within Verve Asset Manager allowin...
As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens' ProductCERT Security Advisories (CERT Services | Services | Siemens Global). View CSAF 1. EXECUTIVE SUMMARY CVSS v4 8.6 ATTENTION: Exploitable remotely/low attack complexity Vendor: Siemens Equipment: LOGO! 8 BM Devices Vulnerabilities: Buffer Copy without Checking Size of Input ('Classic Buffer Overflow'), Missing Authentication for Critical Function 2. RISK EVALUATION Successful exploitation of these vulnerabilities could allow an attacker to execute code remotely, put the device into a denial-of-service state, or change the behavior of the device. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS Siemens reports that the following products are affected: LOGO! 12/24RCE (6ED1052-1MD08-0BA2): All versions SIPLUS LOGO! 12/24RCEo (6AG1052-2MD08-7BA2): All versi...
View CSAF 1. EXECUTIVE SUMMARY CVSS v4 9.3 ATTENTION: Low attack complexity Vendor: Rockwell Automation Equipment: Studio 5000 Simulation Interface Vulnerabilities: Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal'), Server-Side Request Forgery (SSRF) 2. RISK EVALUATION Successful exploitation of these vulnerabilities could allow attackers to trigger outbound SMB requests to capture NTLM hashes and execute scripts with Administrator privileges upon system reboot. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following versions of Rockwell Automation Studio 5000 Simulation Interface are affected: Studio 5000 Simulation Interface: Version 2.02 and prior 3.2 VULNERABILITY OVERVIEW 3.2.1 IMPROPER LIMITATION OF A PATHNAME TO A RESTRICTED DIRECTORY ('PATH TRAVERSAL') CWE-22 A local code execution security issue exists within Studio 5000 Simulation Interface via the API. This vulnerability allows any Windows user on the system to extract files using path traversal...
As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens' ProductCERT Security Advisories (CERT Services | Services | Siemens Global). View CSAF 1. EXECUTIVE SUMMARY CVSS v4 8.7 ATTENTION: Exploitable remotely/low attack complexity Vendor: Siemens Equipment: Spectrum Power 4 Vulnerabilities: Incorrect Use of Privileged APIs, Incorrect Privilege Assignment, Incorrect Permission Assignment for Critical Resource, Inclusion of Functionality from Untrusted Control Sphere 2. RISK EVALUATION Successful exploitation of these vulnerabilities could allow an attacker to remotely execute code as application administrator or locally execute code as operating system administrator. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS Siemens reports that the following products are affected: Spectrum Power 4: Versions prior to V4.70 S...
As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens' ProductCERT Security Advisories (CERT Services | Services | Siemens Global). View CSAF 1. EXECUTIVE SUMMARY CVSS v3 9.3 ATTENTION: Exploitable remotely/low attack complexity Vendor: Siemens Equipment: COMOS Vulnerabilities: Incomplete List of Disallowed Inputs, Cleartext Transmission of Sensitive Information 2. RISK EVALUATION Successful exploitation of these vulnerabilities could allow an attacker to execute arbitrary code or lead to data infiltration. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS Siemens reports that the following products are affected: Siemens COMOS with COMOS Web deployed: Versions prior to 10.4.5 (CVE-2023-45133) Siemens COMOS that use COMOS Snapshots component: Versions prior to 10.4.5 (CVE-2024-0056) 3.2 VULNERABILITY OVERVIEW 3.2....