Security
Headlines
HeadlinesLatestCVEs

Source

us-cert

EFACEC BCU 500

View CSAF 1. EXECUTIVE SUMMARY CVSS v3 9.6 ATTENTION: Exploitable remotely/low attack complexity Vendor: EFACEC Equipment: BCU 500 Vulnerabilities: Uncontrolled Resource Consumption, Cross-site Request Forgery 2. RISK EVALUATION Successful exploitation of these vulnerabilities could allow an attacker to cause a denial-of-service condition on the affected product or compromise the web application through a cross-site request forgery (CSRF) vulnerability. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following version of EFACEC BCU 500, an automation and control IED, is affected: BCU 500: version 4.07 3.2 Vulnerability Overview 3.2.1 UNCONTROLLED RESOURCE CONSUMPTION CWE-400 Through the exploitation of active user sessions, an attacker could send custom requests to cause a denial-of-service condition on the device. CVE-2023-50707 has been assigned to this vulnerability. A CVSS v3 base score of 9.6 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:L/UI:N/S:C/C:N/I:H/A:H). 3.2....

us-cert
#csrf#vulnerability#web#dos
EuroTel ETL3100 Radio Transmitter

View CSAF 1. EXECUTIVE SUMMARY CVSS v3 9.8 ATTENTION: Exploitable remotely/low attack complexity/public exploits are available Vendor: EuroTel Equipment: ETL3100 Vulnerabilities: Improper Restriction of Excessive Authentication Attempts, Authorization Bypass Through User-Controlled Key, Improper Access Control 2. RISK EVALUATION Successful exploitation of these vulnerabilities could allow an unauthenticated attacker to gain full access to the system, disclose sensitive information, or access hidden resources. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following versions EuroTel ETL3100 radio transmitter are affected: ETL3100: version v01c01 ETL3100: version v01x37 3.2 Vulnerability Overview 3.2.1 IMPROPER RESTRICTION OF EXCESSIVE AUTHENTICATION ATTEMPTS CWE-307 EuroTel ETL3100 versions v01c01 and v01x37 does not limit the number of attempts to guess administrative credentials in remote password attacks to gain full control of the system. CVE-2023-6928 has been assigned to this vuln...

EFACEC UC 500E

View CSAF 1. EXECUTIVE SUMMARY CVSS v3 6.3 ATTENTION: Exploitable remotely/low attack complexity Vendor: EFACEC Equipment: UC 500 Vulnerabilities: Cleartext Transmission of Sensitive Information, Open Redirect, Exposure of Sensitive Information to an Unauthorized Actor, Improper Access Control 2. RISK EVALUATION Successful exploitation of these vulnerabilities could allow an attacker to retrieve sensitive information, gain unauthorized access to the product, or redirect users to malicious websites. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following version of EFACEC UC 500E, a HMI, is affected: UC 500E: version 10.1.0 3.2 Vulnerability Overview 3.2.1 CLEARTEXT TRANSMISSION OF SENSITIVE INFORMATION CWE-319 An attacker with network access could perform a man-in-the-middle (MitM) attack and capture sensitive information to gain unauthorized access to the application. CVE-2023-50703 has been assigned to this vulnerability. A CVSS v3 base score of 6.3 has been calculated; the CVSS vec...

Siemens Web Server of Industrial Products

As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens' ProductCERT Security Advisories (CERT Services | Services | Siemens Global). View CSAF 1. EXECUTIVE SUMMARY CVSS v3 7.5 ATTENTION: Exploitable remotely/low attack complexity Vendor: Siemens Equipment: SIMATIC CP, SINAMICS, SIPLUS NET CP Vulnerability: Missing Release of Memory after Effective Lifetime 2. RISK EVALUATION Successful exploitation of this vulnerability could allow an unauthorized attacker with network access to the web server of an affected device to perform a denial-of-service attack. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following products of Siemens, are affected: SIMATIC CP 1242-7 V2 (incl. SIPLUS variants): All versions SIMATIC CP 1243-1 (incl. SIPLUS variants): All versions SIMATIC CP 1243-1 DNP3 (incl. SIPLUS variants): All...

Siemens User Management Component (UMC)

As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens' ProductCERT Security Advisories (CERT Services | Services | Siemens Global). View CSAF 1. EXECUTIVE SUMMARY CVSS v3 7.5 ATTENTION: Exploitable remotely/low attack complexity Vendor: Siemens Equipment: User Management Component (UMC) Vulnerabilities: Permissive Cross-domain Policy with Untrusted Domains, Cross-site Scripting, Classic Buffer Overflow, Improper Input Validation 2. RISK EVALUATION Successful exploitation of these vulnerabilities could lead to a restart of the UMC server. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS Siemens reports the following products are affected: Opcenter Quality: all versions SIMATIC PCS neo: versions prior to v4.1 SINUMERIK Integrate RunMyHMI /Automotive: all versions Totally Integrated Automation Portal (TIA Portal) v...

Siemens OPC UA Implementation in SINUMERIK ONE and SINUMERIK MC

As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens' ProductCERT Security Advisories (CERT Services | Services | Siemens Global). View CSAF 1. EXECUTIVE SUMMARY CVSS v3 7.5 ATTENTION: Exploitable remotely/low attack complexity Vendor: Siemens Equipment: SINUMERIK MC, SINUMERIK ONE Vulnerability: Integer Overflow or Wraparound 2. RISK EVALUATION Successful exploitation of this vulnerability could allow an unauthenticated remote attacker to create a denial of service condition by sending a specially crafted certificate. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following products of Siemens, are affected: SINUMERIK MC: All versions prior to V1.22 SINUMERIK ONE: All versions prior to V6.22 3.2 Vulnerability Overview 3.2.1 INTEGER OVERFLOW OR WRAPAROUND CWE-190 The OPC UA implementations (ANSI C and C++...

Siemens LOGO! and SIPLUS LOGO!

As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens' ProductCERT Security Advisories (CERT Services | Services | Siemens Global). View CSAF 1. EXECUTIVE SUMMARY CVSS v3 7.6 ATTENTION: Low Attack Complexity Vendor: Siemens Equipment: LOGO! and SIPLUS LOGO! Products Vulnerability: Improper Protection against Electromagnetic Fault Injection (EM-FI) 2. RISK EVALUATION Successful exploitation of this vulnerability could cause an electromagnetic fault injection, which would allow an attacker to dump and debug the firmware including memory manipulation. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following products of Siemens, are affected: LOGO! 12/24RCE (6ED1052-1MD08-0BA1): Versions v8.3 and prior LOGO! 12/24RCEo (6ED1052-2MD08-0BA1): Versions v8.3 and prior LOGO! 24CE (6ED1052-1CC08-0BA1): Versions v8.3 ...

Siemens SIMATIC STEP 7 (TIA Portal)

As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens' ProductCERT Security Advisories (CERT Services | Services | Siemens Global). View CSAF 1. EXECUTIVE SUMMARY CVSS v3 4.2 ATTENTION: Low attack complexity Vendor: Siemens Equipment: SIMATIC STEP 7 (TIA Portal) Vulnerability: Cleartext Storage of Sensitive Information in Memory 2. RISK EVALUATION Successful exploitation of this vulnerability could allow a local attacker to gain access to the access level password of the SIMATIC S7-1200 and S7-1500 CPUs, when entered by a legitimate user in the hardware configuration of the affected application. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following Siemens product is affected: SIMATIC STEP 7 (TIA Portal): All versions prior to V19 3.2 Vulnerability Overview 3.2.1 CLEARTEXT STORAGE OF SENSITIVE INFORMATI...

Siemens SIMATIC and SIPLUS Products

As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens' ProductCERT Security Advisories (CERT Services | Services | Siemens Global). View CSAF 1. EXECUTIVE SUMMARY CVSS v3 7.5 ATTENTION: Exploitable remotely/low attack complexity Vendor: Siemens Equipment: SIMATIC and SIPLUS products Vulnerabilities: Uncontrolled Recursion, Buffer Access with Incorrect Length Value 2. RISK EVALUATION Successful exploitation of these vulnerabilities could allow an unauthorized attacker with network access to the web server to perform a denial-of-service attack. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following products of Siemens, are affected: SIMATIC S7-400 CPU 412-2 PN V7 (6ES7412-2EK07-0AB0): All versions SIMATIC S7-400 CPU 414-3 PN/DP V7 (6ES7414-3EM07-0AB0): All versions SIMATIC S7-400 CPU 414F-3 PN/DP V7 (6ES74...

Johnson Controls Kantech Gen1 ioSmart

View CSAF 1. EXECUTIVE SUMMARY CVSS v3 7.5 ATTENTION: Exploitable from adjacent network Vendor: Sensormatic Electronics, LLC, an affiliate of Johnson Controls Inc. Equipment: Kantech Gen1 ioSmart card reader Vulnerability: Missing Release of Memory after Effective Lifetime 2. RISK EVALUATION An attacker with physical access to the Kantech Gen1 ioSmart card reader in certain circumstances can recover the reader's communication memory between the card and reader. 3. TECHNICAL DETAILS 3.1 AFFECTED PRODUCTS The following versions of Kantech Gen1 ioSmart card reader are affected: Kantech Gen1 ioSmart card reader: firmware versions prior to 1.7.2 3.2 Vulnerability Overview 3.2.1 MISSING RELEASE OF MEMORY AFTER EFFECTIVE LIFETIME CWE-401 Kantech Gen1 ioSmart card readers with firmware versions prior to 1.7.2 do not properly release memory after its effective lifetime. An attacker with physical access to the Kantech Gen1 ioSmart card reader in certain circumstances can recover the reader's com...